When ns plug-in a conventional heating pad or a hair dryer into any bedroom duplex, the lights dim; and/or trips the circuit breaker. The house is of new construction-- inserted in service 31 Dec 2013. My inquiry is: deserve to I safely replace the present 15 AMP Breaker v that of a 20 AMP? . . . The company cable is that 14 Gauge Copper Conductor.


*

*

No!

The just safe method to rise the circuit"s volume is by replacing the wire with one of adequate gauge. Because that 20 amps, 12 AWG copper is enough for up to about 100 feet.

You are watching: Can i change a 15 amp breaker to a 20

If you just replace the breaker, the wire have the right to overheat and also ignite the structure from within the walls.

To deal with the dimming issue, examine that the outlet is in good condition and that the wires are securely fastened and not showing any signs that overheating: blackening or loss of the copper shininess. Also, check the finish of the wire within the company panel, both neutral and also "hot" (black) wire. If those room okay, set the appliances come a lower wattage setup or replace them with reduced wattage models.


re-superstructure
improve this answer
follow
edited Dec 20 "13 at 20:23
answer Dec 11 "13 at 0:14
*

wallykwallyk
12k11 gold badge2020 silver- badges4949 bronze badges
1
include a comment |
4
Absolutely NOT.

National Fire Protection company (NFPA) traditional Number 70, National electric Code (NEC), embraced by many states (exceptions room Missouri, Mississippi and also Arizona), requires the branch circuit Over current Protection maker (OCPD --typically a circuit breaker (CB) nowadays, fairly than a fuse native days that yore) to safeguard the cable/wiring buried in your walls from overheating by de-energizing (shut off/open circuit) all outlets (lighting & receptacles) for that circuit through tripping/blowing.

Lights dimming and CBs popping is a sure authorize your house was not built to manage heating blankets and hair dryers in the bedroom. Swapping the end a 20 amp breaker for the 15 amp breaker will violate NEC 210.19(A)(1) and provide cause for your insurance company not to reimburse your losses native fire & smoke damage and also the water damages from the fire room flooding her house.

Wire is made smaller when produced by drawing/stretching it. The much more times its extended the smaller sized it gets. This is why American cable Gauge (AWG) seems backwards, i.e. 14AWG has a smaller sized diameter 보다 10AWG due to the fact that it was extended more.

15 amp rated circuit breakers use 14 AWG present carrying conductors (black warm & white neutral) + a eco-friendly ground wire which usually carries no present in sector standard external white non-metallic sheathed cable dubbed NM-B 90 level Centigrade rated "Romex".

20 amp rated circuit breakers usage the same configuration yet 12 AWG, which is a larger diameter wire than 14 AWG, and also therefor has less resistance for the same distance/footage from the pack center/panelboard circuit breakers. 12 AWG NM-B sheathing is fancy yellow.

10 AWG through orange sheathing would be even better electrically, but more expensive and also not required by "code", the NEC.

Blame every this mumbo jumbo ~ above Physics and also a German called Georg Simon Ohm who created a legislation that even Donald J. Trump card can"t repeal. Voltage ns (V) = present (i amps) time resistance (r ohms). And also Power ns = existing squared (i to the twoth power) times resistance (R).

When you attract too much current through a thin wire, due to the fact that its no a superconductor, you"re converting electric energy right into heat power from Ohm"s resistive loss, resulting in less electrical energy (a voltage drop) reaching your pack (appliance, irradiate bulb, stereo, ...). The excess warm in the wire and also inside your wall surface causes the insulation to fail end time, developing a potential short circuit attach by sparks the ignite flammables.

Have a licensed and also insured electrician (Journeyman or Master) or electrical contractor include a brand-new 20 amp circuit, or replace the currently 14 AWG cabling through 12 AWG cabling, or use your hair dryer in the bathroom i m sorry should already have a GFCI per NEC 210.8(A)1) and 20 amp receptacle per NEC 210.11(C)3) installed within three feet of the sheet of a basin per NEC short article 200, ar III compelled Outlets, 210.52 populated Unit Receptacle Outlets, (D) Bathroom.